• RecommendMORE

    Off grid VMII Plus 3.5KW /5KW MPPT so

    Off grid VMII Plus 3.5KW /5KW MPPT so

    Rack Mount UPS

    GR 1KVA-3KVA

    Date:2017-04-10
    Share


     

    Ture double conversion 1Kva - 3KVA Online UPS, 220V /110V Pure Sine Wave UPS System

      

    Product Features:
     
    * High precision double loaded design
    * Input power factor correction
    * Power factor 0.8
    * Built - precision micro-processing controller
    * External generator
    * Wide input voltag range
    * ECO energy saving mode setting
    * Smart SNMP,USB & RS232 optional





    Specifications:

    Model 1KR/L 2KR/L 3KR/L
    Capacity 1KVA/900W 2KVA/1800W 3KVA/2700W
    Input Nominal Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC
    Voltage Range

    55-

     

     145VAC or 110300VAC at 50% load                                                                               

       85-140VAC or 160-280VAC at 100% load

    Frequency 40-60Hz / 50-70Hz
    Power Factor 0.99
    Output Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC
    Voltage Regulation ±1%

    Frequency Range 

    (Synchronized Range)

    47-53HZ or 57-63HZ

    Frequency Range     

        (Batt. Mode)

    50HZ±0.25HZ or 60HZ±0.3HZ 
    Current Crest Ratio 3:1
    Harmonic Distortion ≤3% THD(Linear load)  ≤6% THD(Non-linear load)  
    Transfer Time 0ms
    WaveForm Pure Sinewave
    Efficiency AC Mode 88% 89% 90%
     Battery Mode 83% 87% 88%

    Battery    

     (Standard Model)

    Battery Type 12V9AH 12V9AH 12V9AH
    Numbers 2PCS 4PCS 6PCS
    Typical Recharge Time 3 hours recover to 90% capacity
    Charging Current 1A
    Charging Voltage 27.4VDC ± 1% 54.7 VDC ±1% 82.1 VDC ±1%

    Battery         

     (Long-run Model)

    Battery Type Depending on the capacity of external batteries
    Numbers 3 6 6
    Charging Current 1.0A/2.0A/4.0A/6.0 A
    Charging Voltage 41.0VDC ± 1% 82.1 VDC ±1% 82.1 VDC ±1%
    Indicators LCD Panel

    UPS status, Load level, Battery level, Input/Output voltage, 

    Discharge timer, and Fault conditions

    Alarm Battery Mode Sounding every 4 seconds
    Low Battery Sounding every second
    Overload Sounding twice every second
    Fault Continously sounding

    Physical

    (Standatd Model)

    Dimension,D*W*H(mm) 310*438*88(2U) 410*438*88(2U) 630*438*88(2U)
    Net Weight(kgs) 12 19 29.3

    Physical

    (Long-run Model)

    Dimension,D*W*H(mm) 310*438*88 410*438*88
    Net Weight(kgs) 9 12 14.2
    Environment Humidity 20-90 % RH @ 0- 40°C (non-condensing)
    Noise Level Less than 50dBA @ 1 Meter
    Management Smart RS232/USB

    Supports Windows 2000/2003/XP/Vista/2008/7/8, 

    Linux, Unix, and MAC

    Optional SNMP Power management from SNMP manager and web browser