    Ture double conversion 6Kva - 10KVA Online UPS,  Pure Sine Wave UPS System

      

    Product Features:
     
    * Ture double-conversion
    * Output power factor 0.8 
    * Wide input voltage (110V-300V)
    * Converter mode available
    * ECO mode for energy saving (only available for 1-3kva)
    * Generator compatible
    * Smart SNMP works well with either USB or RS-232 together
    * Emergency power off function (EPO) only available for 6K/10K models
    * Adjustable charging current via LCD or software (1A-6A ) only available for 6K/10K
    * Input power factor correction






    Specifications:
     
    Model C6K(L) C10K(L)
    Phase 1 phase in/1 phase out
    Capacity 6000VA/4800W 10000VA/8000W
    Input



     
    Norminal Voltage 208/220/230/240VAC
    Voltage Range Low Line Loss 110 VAC ± 3% at 50% Load
    176 VAC ± 3% at 100% Load 
    Low Line Comeback 120 VAC ± 3% at 50% Load
    186 VAC ± 3% at 100% Load 
    High Line Loss 300 VAC ± 3% 
    High Line Comeback  290 VAC ± 3% 
    Frequency Range 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
    Power Factor ≥ 0.99  @ 100% load
    Output


     
    Nominal Voltage  208/220/230/240VAC
    AC Voltage Regulation  ± 1%
    Frequency Range (Synchronized Range) 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
    Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
    Current Crest Ratio 3:1 (max.)
    Harmonic Distortion ≤ 3 % THD (Linear Load) 
    ≤ 6 % THD (Non-linear Load)
    Transfer Time Bypass to Inverter (Line mode) Zero
    Inverter to Bypass (Line mode) Zero
    Waveform (Batt. Mode) Pure Sinewave
    Efficiency Line Mode 89% 90%
    Battery Mode 88% 89%
    Battery Standard Model Battery Type 12V/7AH 12V/9AH
    Numbers 16
    Typical Recharge Time 9 hours recover to 90% capacity
    Charging Current  Default:1.0 A ±  10%, Max.:2.0A ±  10%
    Float Charging Voltage  218.4 VDC ±  1%
    Long-run Model Battery Type Depending on applications
    Numbers 16-20** (adjustable)
    Charging Current  Default:4.0 A ±  10%, Max.:6.0A ±  10%
    Float Charging Voltage  273 VDC ±  1% (based on 20 pcs batteries)
    Indicators LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
    Alarm Battery Mode Sounding every 4 seconds
    Overload Sounding twice every second
    Fault Continuously sounding
    Physical Standard Model Dimension, D X W X H (mm) 369 x 190 x 688 442 x 190 x 688
    Net Weight (kgs) 60 75
    Long-run Model Dimension, D X W X H (mm) 369 x 190 x 318 442 x 190 x 318
    Net Weight (kgs) 21 23
    Environment Operation Humidity 0-95 % RH @ 0- 40°C (non-condensing)
    Noise Level Less than 55dBA @ 1 Meter Less than 58dBA @ 1 Meter
    Management Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC
    Optional SNMP Power management from SNMP manager and web browser